Continuously transposed conductor for power transformer windings: enameled copper strands transposed in a continuous sequence, paper or netting wrapped, built to your cable design.
| Size range | Strand b/a 2.5–7.5; width up to 26 mm |
|---|---|
| Conductor | Copper |
| Thermal class | 105, 120 °C |
| Standards | IEC, NEMA, GB, JIS |
| MOQ | 1,000 kg |
| Lead time | 30–45 days |
A CTC cable is a bundle of enameled rectangular strands arranged in two stacks, with one strand transposed from stack to stack at regular intervals. Every strand occupies every position along the winding, so circulating currents and eddy losses fall sharply compared with a single large conductor.
We build CTC from polyvinyl acetal enameled copper strands, wrapped with kraft paper or polyester netting. Epoxy-bonded versions can be quoted where short-circuit strength is critical.
Continuous transposition equalises strand impedance.
One cable replaces many parallel conductors, cutting winding time.
Compact cable raises the copper fill in the winding.
Strand count, size and covering made to your cable sheet.
| Strand conductor | Enameled rectangular copper |
|---|---|
| Strand enamel | Polyvinyl acetal, Class 120 |
| Strand ratio | 2.5 < b/a < 7.5 |
| Strand width | Up to 26 mm (excluding insulation) |
| Outer covering | Kraft paper or cotton/polyester netting |
| Standards | IEC, NEMA, GB, JIS |
| Certification | ISO 9001, RoHS |
| Packing | Large steel or wooden drums |
| MOQ | 1,000 kg |
| Lead time | 30–45 days |
Sizes and builds outside this table can be made on request. Tell us the dimension, insulation and standard and we will confirm feasibility.
| Spools | Large steel or wooden drums |
|---|---|
| Outer packing | Cartons or fumigation-free wooden pallets, moisture-proof film |
| Labels | Size, insulation, thermal class, net weight, lot number, date; OEM labels available |
| MOQ | 1,000 kg |
| Lead time | 30–45 days |
| Trade terms | FOB Shanghai, CIF, DAP; T/T or L/C at sight |
| Samples | Free sample spool with test report |
A cable of enameled flat strands arranged in two stacks, with strands moved from one stack to the other at regular intervals so each strand occupies every position. It reduces circulating current losses in large windings.
Strand dimensions, number of strands, enamel type, transposition pitch, outer covering, and total length per drum.
Yes, on request, for windings that need higher short-circuit strength.